Prima — Service Level Agreement · KOM Muscat · A4 · 16pp · Draft v0.1
DRAFT
Draft
Part ofPetroCompute
Service Level Agreement
KOM Oman AI Factory
99.982% service level
commitments

Availability, environmental envelope, incident response, service credits and termination triggers for committed GPU capacity at Knowledge Oasis Muscat. Issued for customer, partner and lender review.

Document
PRM-SLA-2026-001
Version
0.1 — Draft
Issued
July 2026
Owner
Office of the COO
Site
Knowledge Oasis Muscat
99.982%
Committed cluster
availability
W27
ASHRAE liquid class
· A2 air-side
15min
P1 incident
response target
24×7
Operations &
monitoring
Basis of this document

The commitments set out here are the operating consequence of how the facility is built: a Tier III Standard design with concurrently maintainable power and cooling, direct liquid cooling throughout at a design PUE of 1.44, and a resident organisation running the data halls and a continuously staffed Network Operations Centre on a four-shift rotation.

This document is written to be verified rather than accepted. Every commitment states what is measured, where it is measured, over what period, and what happens financially when it is missed. Where a figure carries a margin, the margin is disclosed.

DraftVersion 0.1 is issued for evaluation. Figures are indicative and subject to change until incorporated as a schedule to an executed Master Services Agreement, at which point they become the contractual service levels for the relevant Service Order Form.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  01 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 02 / 16
How to read this document

Sections 01–03 establish scope, vocabulary and what is delivered. Sections 04–06 state the measurable commitments; 07 and 08 the financial consequence of missing them. Sections 09–12 cover the operating disciplines that hold them, and 13–15 the limits, the exit right and the governance around both.

Commitments

Sections 04, 05 and 06. Each states the level, the measurement point and the measurement period.

What we promise
Consequence

Sections 07 and 08. Credits are automatic, tiered and capped, and applied without a claim.

What it costs us
Exit

Section 14. Persistent underperformance is a termination right, not another credit.

Your protection
Relationship to other documents
Master Services AgreementGoverns the commercial and legal relationship. This SLA is intended to attach to it as a schedule; where the two conflict, the Master Services Agreement prevails except on service levels, which are governed here.
Service Order FormIdentifies the Committed Capacity, term and charges for a specific hall or phase. Commitments in this SLA are measured and credited per Service Order Form.
Connectivity SLAWhere external connectivity is contracted, it is covered by a separate service level agreement and is excluded from Cluster Availability.
Acceptable Use PolicyGoverns workload conduct. Availability commitments do not apply to capacity suspended for a breach of that policy.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  02 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 03 / 16
01Scope, structure and summary of commitments

This document sets out the service levels Prima commits to for GPU compute capacity delivered at the KOM Oman AI Factory, Knowledge Oasis Muscat, Sultanate of Oman. It answers four questions a customer, a lender and an insurer each need answered in writing: what availability is promised and how it is measured; what environmental envelope is held at the rack; what compensation applies when the commitment is missed; and at what point persistent underperformance becomes a right to exit.

Commitments apply per Service Order Form and are measured per calendar month against the Committed Capacity for each data hall. Where a Service Order Form covers more than one hall or phase, each hall is measured and credited separately — a good month in one hall does not offset a bad month in another.

Summary of commitmentsPer calendar month · per Service Order Form
CommitmentLevelMeasurement pointSection
Cluster Availability99.982%Committed Capacity at the hall boundary04
Power availability99.982%Rack PDU input, both feeds05
Internal fabric availability99.99%Leaf-switch customer port05
Storage availability99.99%Namespace mount point05
Coolant supply temperatureW27CDU primary inlet06
Air-side envelopeClass A2Rack air inlet, mid-height06
P1 incident response15 minFrom NOC detection or customer ticket09
Smart hands response30 minFrom ticket, 24×7, within committed hours03
Aggregate credit exposureOne monthAll causesPer affected capacity50%
What this document does not coverCovered elsewhere or not contracted
External connectivity and internet transit — separate connectivity SLA
Customer-supplied hardware, firmware and images
Workload performance, throughput or model convergence
Managed platform, MLOps or professional services
Customer data backup beyond the contracted storage tier
Commercial terms, pricing and payment — Master Services Agreement
NoteNo commitment in this document is expressed as a performance figure for the customer's workload. Availability is a statement about infrastructure readiness — power, environment and reachability — and is deliberately independent of what the customer chooses to run on it.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  03 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 04 / 16
02DefinitionsAs used throughout

Capitalised terms have the meanings below. Where a term is also defined in the Master Services Agreement, the definition here applies for the purposes of measuring service levels.

Cluster AvailabilityThe proportion of minutes in a Measurement Period during which the Committed Capacity is powered, held within the Envelope, and reachable at the leaf-switch customer port, expressed as a percentage.
Committed CapacityThe GPU count, rack count and contracted power draw stated in the relevant Service Order Form for a given data hall.
Measurement PeriodA calendar month, running from 00:00 on the first day to 23:59 on the last day, Gulf Standard Time.
Unavailable MinuteAny whole minute within a Measurement Period in which the conditions in the definition of Cluster Availability are not met, net of Excluded Events, pro-rated where only part of the Committed Capacity is affected.
EnvelopeThe coolant-side and air-side environmental parameters committed in section 06.
Excluded EventAn event listed in section 13, and no other.
Monthly Service ChargeThe recurring charge payable under the relevant Service Order Form for the affected capacity for the Measurement Period in question, excluding taxes, connectivity charges, non-recurring charges and pass-through power.
Service CreditThe amount credited to the customer under section 07, expressed as a percentage of the Monthly Service Charge.
P1 · P2 · P3 · P4Incident priority levels as classified in section 09, assigned on service impact rather than on cause.
Response TimeThe interval between the earlier of NOC detection or customer ticket, and the first substantive engineer action recorded against the ticket.
RestorationThe point at which the affected capacity is returned to a state satisfying the definition of Cluster Availability, whether or not root cause has been established.
Planned MaintenanceWork notified in accordance with section 11 and performed within an agreed window.
Emergency MaintenanceWork required to prevent imminent loss of service or a safety hazard, performed without the notice period in section 11.
Maintenance WindowThe standard window defined in section 11, or another period agreed in writing with the customer.
Freeze PeriodA period nominated by the customer under section 11 during which no service-affecting Planned Maintenance will be scheduled.
Service Order FormThe ordering document issued under the Master Services Agreement identifying the Committed Capacity, term and charges. Abbreviated in this document to SOF.
NOCThe Network Operations Centre at the site, staffed continuously, 24 hours a day, every day of the year.
CDUCoolant Distribution Unit — the interface between the facility water system and the secondary loop serving the racks.
GSTGulf Standard Time, UTC+4. All times in this document are GST unless stated otherwise.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  04 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 05 / 16
03Service description and boundariesWhat is delivered

The service is bare-metal GPU capacity in a purpose-built AI facility: racks powered and cooled to the committed Envelope, connected to a non-blocking internal fabric, with resident engineering support. The customer holds the workload; Prima holds everything the workload sits on.

Service elementsIncluded in the Monthly Service Charge
ElementDelivered
SpaceData hallRacks in a Tier III Standard hall, with hot- and cold-side containment and dedicated customer cages where contracted.
PowerConcurrently maintainableDual-fed A and B power to rack PDU, N+1 UPS and generator chain, contracted power draw per rack as stated in the SOF.
CoolingDirect liquidDirect-liquid-cooled racks served from N+1 CDUs and chiller plant; air-side cooling for ancillary equipment in the same hall.
FabricInternalNon-blocking spine-leaf InfiniBand compute fabric, separate Ethernet management and storage networks, customer handover at the leaf-switch port.
StorageWhere contractedHigh-throughput parallel namespace presented to the compute nodes, with capacity and throughput as stated in the SOF.
Smart hands24×7Resident data-hall engineers for cabling, reseats, component swaps, media handling and guided diagnostics, within the hours committed in the SOF.
MonitoringNOCContinuous monitoring of power, environment, fabric and rack reachability, with incident detection and escalation per sections 09 and 10.
ReportingMonthlyMonthly service report per section 15, including measured availability, environmental series, incident record and credits.
DemarcationWhere Prima responsibility ends
Power

Prima to the rack PDU outlet. The customer owns everything downstream of the outlet, including cords, PSUs and in-rack distribution.

Boundary — PDU outlet
Cooling

Prima to the rack manifold or CDU secondary connection. The customer owns cold plates, in-node loops and node-level thermal control.

Boundary — rack manifold
Network

Prima to the leaf-switch customer port. The customer owns host adapters, drivers, fabric tuning and everything above layer 2.

Boundary — leaf port
Customer obligations that bear on the commitmentsPrerequisites
  • Contracted power draw. Operating a rack above the power draw stated in the SOF may take equipment outside the Envelope. Availability is not committed for racks operated above contracted draw.
  • Named contacts. The customer maintains a current escalation list of at least two technical contacts reachable 24×7, and a named commercial contact for the monthly report.
  • Access for restoration. Where physical access to customer-owned equipment is required to restore service, the customer grants or delegates access without undue delay.
  • Change notification. The customer notifies Prima of firmware, image or workload changes materially altering power or thermal profile at least five business days before deployment.
  • Ticket discipline. Availability events are raised through the NOC with timestamps. Informal channels do not start the Response Time clock.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  05 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 06 / 16
04Availability commitment and measurement99.982% monthly

Prima commits to a Cluster Availability of 99.982% per Measurement Period. A minute counts as available only if the Committed Capacity is powered, within the Envelope, and reachable at the leaf-switch customer port. Any whole minute failing any one of those three tests is an Unavailable Minute, whether or not the customer's workload was running at the time.

Cluster Availability = ( Total Minutes − Unavailable Minutes ) ÷ Total Minutes × 100
Total Minutes = calendar minutes in the Measurement Period · Unavailable Minutes = aggregate whole minutes of unavailability, net of Excluded Events, pro-rated by affected share of Committed Capacity
Downtime allowance at 99.982%Derived from the commitment, not additional to it
Measurement PeriodTotal minutesAllowanceExpressed as
Month — 28 days40,3207.26 min7 min 16 s
Month — 30 days43,2007.78 min7 min 47 s
Month — 31 days44,6408.04 min8 min 02 s
Year — 365 days525,60094.6 min1 h 34 min 36 s
Measurement methodologyNOC telemetry is the record of authority
  1. Sampling. Availability inputs are sampled at 30-second intervals across the power chain, CDU and BMS sensors, fabric port state and rack-level reachability probes. A minute is marked unavailable if any sample within it fails.
  2. Ticketing. Every unavailability event is raised as a ticket carrying a start timestamp, restoration timestamp, affected racks, priority and root cause. The ticket record is the sole basis of the reported monthly figure.
  3. Pro-rating. Where only part of the Committed Capacity is affected, Unavailable Minutes are multiplied by the affected share of committed GPUs, rounded up to the nearest whole rack.
  4. Customer-raised events. The customer may raise an availability event through the NOC at any time. Where the customer record and the Prima record differ on start time, the earlier of the two timestamps applies.
  5. Concurrency. Overlapping events are not double-counted; a minute is either available or unavailable, and the highest affected capacity share in that minute is used.
  6. Retention. Availability telemetry and ticket records are retained for 24 months and made available to the customer on request within the retention period.
NoteRestoration is recorded when the capacity is returned to a compliant state, not when root cause is established. A long root-cause investigation does not extend the recorded downtime; an unrestored service does not stop the clock because a cause has been identified.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  06 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 07 / 16
05Component service levelsMeasured independently

Each component of the service carries its own commitment, measured at its own boundary. Component figures are reported separately so that a customer can see where a bad month came from — but a component breach is credited through the Cluster Availability figure it produces, not through a second, parallel credit.

Power99.982% at rack PDU input
TopologyDual independent feeds (A and B) to each rack, N+1 UPS, N+1 standby generation with on-site fuel for 48 hours at full load.
Single-path lossLoss of one of two feeds is not unavailability provided the surviving path carries the load within its rating. It is reported as a P2 incident and a loss of redundancy.
Both-path lossLoss of both feeds to a rack is unavailability for that rack from the first affected minute until restoration.
Utility eventsLoss of utility supply at the site boundary is not an Excluded Event. The generator and UPS chain exists to absorb it; failure to absorb it counts against the commitment.
CoolingEnvelope held per section 06
TopologyN+1 chiller plant and N+1 CDUs, dual-path secondary loops to the rack manifold, thermal ride-through sized to the design load.
Excursion thresholdCoolant supply outside W27 at the CDU primary inlet for more than 15 consecutive minutes is unavailability for the racks served by the affected loop.
Short excursionAn excursion under 15 minutes is reported as an environmental excursion with no availability impact — this is the ride-through the design is built to provide.
Repeat excursionsThree or more excursions in a Measurement Period, of any duration, trigger a written root-cause analysis within 10 business days.
Internal fabric and storage99.99% each
ElementCommitmentMeasurement and treatment
Compute fabricInfiniBand99.99%Measured at the leaf-switch customer port. Loss of a single leaf uplink is not unavailability where the port remains reachable at full rated bandwidth.
Management networkEthernet99.99%Measured at the out-of-band management port. Required for customer diagnostics; measured but excluded from Cluster Availability.
Storage namespaceWhere contracted99.99%Measured at the namespace mount point from a reference client. Degraded throughput above 70% of contracted rate is a P2, not unavailability.
External connectivityWhere contractedSeparateGoverned by the connectivity SLA. Explicitly excluded from Cluster Availability under section 13.
NoteLoss of redundancy is reported and escalated even where service is unaffected. A month in which the service never dropped but ran single-path for three weeks is not a good month, and the monthly report will say so.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  07 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 08 / 16
06Environmental commitment — ASHRAE envelopeW27 liquid · A2 air

The facility is direct-liquid-cooled, so the binding environmental commitment sits on the liquid side — coolant supply temperature at the CDU primary inlet. An air-side commitment applies to ancillary and air-cooled equipment in the same hall. Both are stated against published ASHRAE classes so that compliance is verifiable against an external standard rather than an internal one.

Liquid side — ASHRAE class W27Measured at the CDU primary inlet
ParameterCommittedMeasurement basis
Coolant supply temperature≤ 27 °CInstantaneous, 30-second sampling
Supply temperature stability± 1.5 °CRolling 15-minute mean
Rate of change≤ 5 °C / hrRolling 60-minute window
Differential pressure at manifoldPer designContinuous, per rack manifold
Water quality and filtrationASHRAE 90.1Secondary loop, quarterly assay
Plant capability at N+1W32Design headroom, not the commitment

The plant is capable of W32 operation at N+1; the service is committed at W27. That gap is deliberate and disclosed — it is the margin absorbed during a chiller failure or an ambient extreme without breaching the customer commitment.

Air side — ASHRAE Class A2Measured at rack air inlet, mid-height
ParameterCommitted rangeMeasurement basis
Dry-bulb temperature10 – 35 °CInstantaneous, per cold aisle
Relative humidity20 – 80% RHInstantaneous, per cold aisle
Maximum dew point21 °CHall return air
Rate of change≤ 5 °C / hrRolling 60-minute window
Airborne particulateISO 14644-1 Class 8Annual survey
Excursions and consequenceSection 07 applies where an excursion becomes downtime
Under 15 minutes

Recorded as an environmental excursion in the monthly report. No availability impact and no credit — within designed ride-through.

Reported only
15 minutes and over

Counted as unavailability for the racks served by the affected loop or air path, from the first minute outside the Envelope until restoration.

Counts as downtime
Three or more in a month

Formal root-cause analysis issued to the customer within 10 business days, regardless of individual excursion duration.

Written RCA
DataEnvironmental telemetry is logged by the BMS at 30-second resolution and retained for 24 months. Customers may request the raw series for any period within retention, without charge, as part of the monthly reporting cycle.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  08 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 09 / 16
07Service credits — scheduleCapped at 50% per month

Where measured Cluster Availability for a Measurement Period falls below the commitment, the customer is entitled to a Service Credit expressed as a percentage of the Monthly Service Charge for the affected capacity. Credits are the agreed financial remedy for missed availability and are applied against the following month's invoice.

Credit schedule% of Monthly Service Charge for the affected capacity
TierMeasured Cluster AvailabilityUnavailability, 30-day monthCredit
99.982% and aboveUp to 7 min 47 sMet
01Below 99.982% to 99.500%7 min 47 s – 3 h 36 min10%
02Below 99.500% to 99.000%3 h 36 min – 7 h 12 min25%
03Below 99.000%Over 7 h 12 min50%
Aggregate cap — one monthAll credits, all causes50%
Component and environmental breachesCredited through Cluster Availability
Power, cooling, fabricA breach of a component commitment in section 05 or the Envelope in section 06 is credited through the Cluster Availability figure it produces. It does not attract a second, separate credit.
Loss of redundancyRunning on a single path, where service is carried, produces no credit. It is reported, escalated as a P2, and — if unremedied for more than 30 consecutive days — attracts a credit of 5% for the month in question.
Response-time breachFailure to meet the P1 Response Time in section 09 on two or more occasions in a Measurement Period attracts a credit of 5%, within the aggregate cap.
Reporting failureFailure to issue the monthly service report by the tenth business day attracts a credit of 2%, within the aggregate cap.
Credit exposure at a glancePer hall, per month
First minute past allowance
10%
Tier 01 applies from the first Unavailable Minute beyond 7 min 47 s
Half a working day lost
50%
Tier 03 applies at 7 h 12 min of unavailability in a 30-day month
Maximum monthly exposure
50%
Aggregate cap across every credit head in this section
NoteService Credits are the customer's sole financial remedy for missed availability under this SLA. They do not limit or defer the customer's rights under section 14 where underperformance becomes persistent.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  09 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 10 / 16
08Service credits — application and worked examplesAutomatic, no claim required
Rules of applicationHow a credit reaches the invoice
  1. Single tier per period. Only the tier corresponding to the measured Cluster Availability applies. Tiers are not cumulative and are not stacked.
  2. Per affected capacity. The credit is calculated on the Monthly Service Charge for the racks or hall that missed the commitment — not on the whole contract.
  3. Issued by Prima. Credits are identified in the monthly service report and applied automatically to the next invoice. The customer is not required to claim them.
  4. Aggregate cap. Total credits in any Measurement Period, from every head in section 07, will not exceed 50% of the Monthly Service Charge for the affected capacity.
  5. No set-off against power. Credits are calculated on the service charge only, and are not netted against pass-through power, taxes or non-recurring charges.
  6. Credit, not refund. Credits are applied against amounts otherwise payable. On termination with a credit balance outstanding, the balance is paid in cash within 30 days of final invoice.
  7. Survives assignment. Accrued credits follow the SOF on any permitted assignment or novation.
Worked example A — cooling-plant faultIllustrative
ScenarioA hall carrying 1,008 GPUs experiences a chiller fault. Coolant supply at the CDU primary inlet is above 27 °C for 4 h 10 min. No other unavailability in the month. 30-day month.
Unavailable Minutes250 minutes, all racks in the hall affected — no pro-rating applies.
Measured availability(43,200 − 250) ÷ 43,200 × 100 = 99.421%
Tier appliedTier 02 — below 99.500% to 99.000% → 25% credit
Credit25% of the Monthly Service Charge for the 1,008 GPUs in the affected hall, applied to the following month's invoice, plus a written root-cause analysis within 5 business days.
Worked example B — partial capacity, pro-ratedIllustrative
ScenarioA hall carrying 10,000 GPUs across 125 racks loses both power feeds to 4 racks (320 GPUs) for 6 hours. 30-day month.
Affected share4 racks ÷ 125 racks = 3.2% of Committed Capacity.
Unavailable Minutes360 raw minutes × 3.2% = 11.52 pro-rated Unavailable Minutes.
Measured availability(43,200 − 11.52) ÷ 43,200 × 100 = 99.973%
Tier appliedTier 01 — below 99.982% to 99.500% → 10% credit
Credit10% of the Monthly Service Charge for the whole hall — not 10% of the four racks. Pro-rating applies to the downtime calculation, not to the credit base.
NoteExample B is the important one. Pro-rating reduces the measured downtime, so a small partial outage is unlikely to reach a high tier — but the credit, once triggered, is calculated on the full Monthly Service Charge for the hall. That asymmetry is intentional and in the customer's favour.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  10 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 11 / 16
09Incident classification and responseP1 — 15 minutes

Incidents are classified on service impact, not on cause. Response Time runs from the earlier of NOC detection or customer ticket. Every response target below is met by the resident 24×7 team — there is no dependence on business-hours coverage or on-call callout for P1 and P2.

Priority matrixResponse · updates · target restoration
LevelDefinitionResponseUpdatesTarget restore
P1CriticalLoss of power, cooling or fabric to Committed Capacity; capacity unusable15 minEvery 60 min4 hours
P2HighDegraded operation or loss of redundancy; service carried on a single path1 hourEvery 4 hours24 hours
P3MediumNon-service-affecting fault; single node, port or component4 hoursDaily5 business days
P4LowSmart hands, scheduled requests, information and access requestsNBDOn completionAs agreed
Classification examplesIndicative, not exhaustive
P1 — Critical

Both power feeds lost to a rack row · coolant supply above 27 °C for over 15 minutes · leaf-switch group down · hall-wide fabric partition · fire-system activation in an occupied hall.

Continuous work until restored
P2 — High

Single power feed lost · one of two CDUs offline · single leaf uplink down with port reachable · storage throughput below 70% of contracted rate · UPS on bypass.

Redundancy restored as priority
P3 — Medium

Single node unreachable · one optic degraded · non-critical sensor fault · BMS alarm without environmental impact · cosmetic or documentation defect.

Scheduled into normal work
P4 — Low

Cable moves and adds · media handling · scheduled reseat · visitor and escort requests · asset audit · information requests.

Within committed smart-hands hours
ReclassificationIn both directions
  • Upgrade on customer request. The customer may request an upgrade in priority at any time; the request is honoured for one level unless Prima can demonstrate on the telemetry that impact does not warrant it.
  • Downgrade requires agreement. Prima will not downgrade a P1 or P2 without the customer's written agreement or restoration of service.
  • Clock does not reset. Reclassification does not restart the Response Time clock; the original detection or ticket timestamp continues to apply.
  • Ageing. A P3 unresolved beyond its target restoration is escalated automatically to P2. A P2 unresolved beyond 48 hours is escalated automatically to P1.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  11 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 12 / 16
10Escalation, root-cause analysis and communicationTime-based, automatic

Escalation is driven by the clock, not by the customer. A P1 reaches executive level on a fixed schedule whether or not the customer asks for it, and the customer is told at each step.

Escalation ladder — P1Cumulative from detection
Level 1
NOC Engineer
On detection
Level 2
Shift Lead
+ 15 minutes
Level 3
Operations Manager
+ 60 minutes
Level 4
Chief Operating Officer
+ 2 hours
Level 5
Chief Executive Officer
+ 8 hours

A P1 unresolved at two hours is on the COO's desk with a written status; at four hours it produces a formal incident notice to the customer's named contacts within the hour; at eight hours it is a CEO-level matter with a written recovery plan.

Root-cause analysisIssued in writing, without request
TriggerDeadlineContents
Every P15 bus. daysTimeline to the minute, immediate and underlying cause, restoration actions, availability impact quantified, preventive measures with named owners and dates.
P2 affecting redundancy10 bus. daysCause, restoration of redundancy, and whether the event indicates a systemic weakness.
Recurrence10 bus. daysAny incident of the same cause recurring within a quarter, with an explanation of why the previous preventive measure did not hold.
Three excursions10 bus. daysEnvironmental root-cause analysis per section 06, whatever the individual excursion durations.
Communication channels24×7 for P1 and P2
NOC hotlineStaffed continuously. Primary channel for P1 and P2. Calls are logged and produce a ticket automatically.
Ticket portalPrimary channel for P3 and P4, and the system of record for all priorities. Customer-visible timestamps, status and engineer notes.
Named escalation listPrima maintains a current list of Level 2 to Level 5 contacts with direct numbers, reviewed quarterly and reissued on any change.
Status notificationsPush notification to customer named contacts on P1 raise, on each scheduled update, and on restoration.
Service review cadenceStanding governance
Monthly — report

Written service report per section 15, issued by the tenth business day. No meeting required.

Ops Manager
Quarterly — review

Service review covering availability trend, open preventive actions and maintenance performance.

Ops Manager + CCO
Annual — assurance

Review of the SLA against actual performance, with any proposed amendment tabled in writing.

COO
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  12 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 13 / 16
11Planned maintenance and change controlConcurrently maintainable

The facility is designed to Tier III Standard — every element of the power and cooling path can be taken out of service for maintenance without interrupting the load. Planned Maintenance is therefore expected to be non-disruptive, and non-disruptive work does not consume the customer's availability allowance.

Maintenance classesNotice · window · availability treatment
ClassNoticeWindowAvailability treatment
Non-disruptive7 calendar daysAny timeNot counted as unavailability.
Standard, service-affecting14 calendar daysAgreed windowExcluded where performed within the agreed window and within the annual allowance.
EmergencyAs early as practicableImmediateCounted as unavailability and credited under section 07.
Customer-requestedBy agreementBy agreementNot counted as unavailability.
Windows and allowancesGulf Standard Time
Standard window

Sunday 01:00 – 05:00 GST, up to twice per calendar quarter for service-affecting work. Work outside the window requires customer consent, which will not be unreasonably withheld.

Two windows per quarter
Annual allowance

Service-affecting Planned Maintenance is capped at 16 hours per year in aggregate. Time beyond the cap is counted as unavailability regardless of notice given.

16 hours per year
Freeze periods

The customer may nominate up to four Freeze Periods per year, of up to seven days each, during which no service-affecting Planned Maintenance will be scheduled.

Customer nominated
Cancellation

A notified window may be cancelled by either party up to 24 hours before it opens, with no obligation on the customer and no consumption of the annual allowance.

24-hour cancellation
Change controlOwned by Facilities and Engineering
  1. Preventive maintenance programme. A published annual calendar covering the electrical chain, cooling plant, generators, fire systems and fabric, executed by the resident Facilities team with OEM vendors under supervision.
  2. Change approval. Any change touching the critical path requires written approval from the Facilities Manager and the Operations Manager, with a documented rollback plan and rollback trigger recorded before work begins.
  3. Customer-affecting change. Notice is issued to the named customer contacts with scope, window, expected impact, rollback trigger and the engineer accountable on the night.
  4. Post-change verification. Environmental and availability telemetry is verified against the pre-change baseline before the window is closed; the result is recorded in the monthly report.
  5. Failed change. Where a change is rolled back and the window overruns, the overrun is treated as Emergency Maintenance and counted as unavailability.
NoteEmergency Maintenance is counted as unavailability and attracts credits. The design intent is that emergency work should be rare; this SLA is written so that it costs Prima when it is not.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  13 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 14 / 16
12Security, access and complianceService levels on access and assurance

Physical and information security are operated in-house. This section states the service levels attaching to them — access provisioning times, incident notification obligations and the assurance programme the customer can rely on in its own audits.

Physical access service levelsFrom a complete request
RequestTargetNotes
Permanent access — new authorised person3 bus. daysSubject to background screening and induction
Scheduled visit — escorted1 bus. dayNamed visitors, 24 hours' notice
Emergency access — out of hours2 hoursAuthorised persons only, escorted
Access revocation1 hourOn written request, 24×7
Security controls in placeOperated at the site
·24×7 manned perimeter and reception, under managed-service contract supervised by the COO
·Multi-factor access control to hall and cage level, with per-person audit trail
·CCTV coverage of perimeter, entries, aisles and cage doors, retained per policy
·Escort requirement for non-authorised persons in technical space
Security incident notificationObligation on Prima
Confirmed breachNotification to the customer's named security contact within 24 hours of confirmation, with the facts known at that point and a committed time for the next update.
Suspected breachNotification within 72 hours of escalation to the CISO, where the customer's capacity or data may be affected.
Written reportFull written report within 10 business days of confirmation, covering containment, scope and remediation.
RegulatoryPrima will cooperate with any notification the customer is required to make to a regulator, and will not require a separate request to do so.
Assurance and certificationProgramme status
FrameworkStatusCustomer entitlement
ISO/IEC 27001Programme in implementationCurrent certificate and scope statement on request once certified; interim control summary available now.
SOC 2 Type IIProgramme in implementationReport on request under NDA once available, annually thereafter.
Uptime InstituteTier III Standard — designDesign documentation on request under NDA.
Customer auditPermittedOne on-site audit per contract year on 30 days' notice, at customer cost, subject to site safety and other customers' confidentiality. Certification status is stated as at the issue date of this draft and will be restated on execution.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  14 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 15 / 16
13ExclusionsClosed list
Planned MaintenanceNon-disruptive work, and service-affecting work performed within an agreed Maintenance Window and within the annual allowance in section 11.
Customer actsFaults caused by customer hardware, firmware, software, configuration or workload, including thermal or power excursions induced by customer-side changes, and operation above contracted power draw.
Customer accessRefusal or undue delay of access required to diagnose or restore, where access was requested in accordance with section 10.
External connectivityFaults beyond the leaf-switch customer port, including carrier and internet-transit events, covered by the separate connectivity SLA where contracted.
Force majeureEvents beyond reasonable control as defined in the Master Services Agreement, subject to Prima performing its business-continuity obligations.
Suspension for causeSuspension properly exercised under the Master Services Agreement, including for non-payment or a security event attributable to the customer.

The list above is exhaustive. Any cause of unavailability not on it counts against the commitment — including, for the avoidance of doubt: OEM and subcontractor failure; utility loss at the site boundary; fuel supply failure; failure of Prima-owned or Prima-operated equipment; staffing shortfall; and failure of a managed-service provider engaged by Prima.

BurdenWhere Prima asserts an Excluded Event, the burden of demonstrating it sits with Prima, on the telemetry and ticket record, in the monthly service report. An assertion without evidence does not reduce measured unavailability.
14Termination triggers and remediationExit right on persistent breach

Service Credits compensate a bad month. They are not a substitute for a service that works. Where availability is persistently below commitment, the customer may terminate the affected SOF without termination charge and without loss of any accrued credit, on thirty (30) days' written notice, if any of the following occurs.

Trigger 01 — single severe month

Measured Cluster Availability falls below 95.000% in any single Measurement Period.

One month
Trigger 02 — three consecutive

Measured Cluster Availability falls below 99.982% in three consecutive Measurement Periods.

Consecutive
Trigger 03 — chronic

Measured Cluster Availability falls below 99.982% in any four Measurement Periods within a rolling twelve-month window.

Rolling 12 months
Remediation before terminationPrima obligation, not customer option
  • Remediation plan. On the second consecutive Measurement Period below commitment, Prima issues a written remediation plan within ten business days, with named owners and dated milestones.
  • Executive review. The plan is reviewed with the customer at COO level monthly until availability has been at or above commitment for two consecutive Measurement Periods.
  • Right preserved. Accepting or participating in a remediation plan does not waive or defer the termination right once a trigger above is met.
  • Orderly exit. On termination for a trigger, Prima supports migration of the customer's workload and data for up to ninety (90) days at the then-current rate, with no exit, de-installation or early-termination fee.
  • Per SOF. Triggers attach to the affected SOF, not to the Master Services Agreement. A customer terminating one hall retains all rights and pricing under any other SOF in force.
© 2026 Prima Artificial Intelligence LLC · Sultanate of OmanDraft v0.1 · July 2026  15 / 16
DRAFT
PRIMA
Service Level AgreementKOM Oman AI Factory · 16 / 16
15Reporting, claims and governanceMonthly, in writing

Prima reports against every commitment in this document each month, without a request, by the tenth business day following the Measurement Period. The report is the single document in which measured performance, credits and open actions are reconciled.

Monthly service reportContents
SectionDetail
AvailabilityMeasured Cluster Availability, component availability, Unavailable Minutes with the ticket reference and affected capacity share for each event.
EnvironmentalCoolant-supply and rack-inlet series against the Envelope, every excursion listed, classified and durated.
IncidentsAll P1 and P2 tickets with Response Times against target, restoration times and root-cause-analysis status.
MaintenanceWork performed, class, window compliance and cumulative position against the annual allowance.
ExclusionsEvery Excluded Event relied on, with the evidence supporting it.
CreditsTier reached, credit percentage under each head, affected capacity and the invoice against which the credit is applied.
Queries and disputes30-day window
Raise

The customer may query a reported figure within 30 days of the report, stating the events and periods in question.

Written notice
Substantiate

Prima provides the underlying telemetry and ticket record within 10 business days, without charge.

Raw data on request
Resolve

Unresolved after 20 business days, the query escalates to COO level; failing that, to the dispute process in the Master Services Agreement.

COO, then MSA process
Amendment and reviewGovernance
Annual reviewThis SLA is reviewed annually against actual performance. Any proposed amendment is tabled in writing at least sixty (60) days before it would take effect.
No unilateral reductionNo commitment in this document may be reduced without the customer's written agreement.
ImprovementWhere sustained performance exceeds a commitment for four consecutive quarters, Prima will table a proposal to raise the committed level.
PrecedenceOn service levels this document prevails over the Master Services Agreement and over any Prima standard terms. On all other matters the Master Services Agreement prevails.
Office of the Chief Operating Officer

For questions on this document, the measurement methodology or the underlying telemetry. Figures are indicative; service levels are finalised on incorporation as a schedule to an executed Master Services Agreement.